Networks of sensors and data validation

 

Strategies for the validation and reconstruction of data


ValidacionDatos.jpg
The validation of data consists on capturing the data with a regular temporary frequency (for example hourly) from the operational data base of the system of telecontrol, which allow to know periodically (once a day) the state of the network, or through express request of the operator of the system of telecontrol, to analyze with different levels of test all the data of the interval concerned and, from the result obtained,  to label the data as valid data, specifying  the tests passed  or non-passed, specifying which are the non-passed tests and keeping them  in the same operating data base of the system of telecontrol.

The collection of tests that has to pass each one of the data with a regulalr frequency (every 10 minutes, hourly or daily) of the state of the network, is inspired in the levels of data quality of the defined automatic meteorological stations, according to the regulation UNE 500540.

 

  • Test 1. Errors of communication: it is a matter of knowing if the datum has arrived or not  in the expected moment (every 10 minutes, hourly or daily).
  • Test 2. It is analyzed if a datum exceeds the maximum or minimum physical values, impossible to be exceeded for a coherent datum.
  • Test 3. The temporary variation of the datum is analyzed, since the difference between two consecutive values should not exceed certain values of reference.
  • Test 4. It is analyzed if the sensors of a same station are coherent among them. For example, if the position of a valve indicates that it is closed, water can not circulate and the sensor of flow has to indicate zero or a value very near to zero.
  • Test 5. It is analyzed the space coherence of the data of the network, from a model of relation among measures; and
  • Test 6. The temporary coherence of the data is analyzed and the estimation of the datum is compared from all its history to the datum to be validated.

If a datum does not pass one of these tests, the datum is not reliable and it has to be reconstructed through the application of one or several models (analytical redundancy), that would allow to estimate its value.

This methodology has already been implemented in the Barcelona distriibution network,  that has 400 devices to measure the waterflow and at present is implementing hourly and daily data from the network of water transport of ATLL. It is considered that it will be a great benefit to increase the confidence in the data of the system of telecontrol and its subsequent exploitation to carry out a proper management of the network, as it could well be the calculation of the water performance of the different sectors of the network and/or the detection of water leakages.